NIK 2300

Three-phase meter

  • Measurement with accuracy class 0,5 S
  • DLMS
  • Active + reactive energy
  • Transparent case
  • 4 tariffs / 12 zones
  • Optical port
  • Sensors of magnetic and electromagnetic fields
  • Tamper sensor for case and terminal cover
  • Two batteries / Battery mode
  • Instantaneous values of power, voltage, amperage
  • Voltage quality control with measurement
    of voltage harmonics
  • «RESET» button with configurable actions
  • LCD with vector diagram and OBIS codes
  • Terminal block
  • Data protection by encryption
  • Remote firmware update
  • Operation voltage range from 100...400 V for transformer connection
  • Disconnector with a current of 100 A
Meter type

Electronic, Electronic

Number of phases

Three-phase, Three-phase

Active / reactive energy:

A, A, AR, AR

Accuracy class of active energy measurement:

0,5 S, 0,5 S, 1, 1

Fraud protection

Electromagnetic field indication, Electromagnetic field indication, Indication of the magnetic field, Indication of the magnetic field, Mechanical intervention sensors, Mechanical intervention sensors

Interfaces

Optical port, Optical port, PLC, PLC, PLC DCSK, PLC DCSK, PLC-G3, PLC-G3, RF 2,4 Ghz, RF 2,4 Ghz, RF Plug&Play 2.4 GHz, RF Plug&Play 2.4 GHz, RF SubGHz 868 MHz, RF SubGHz 868 MHz, RS-485, RS-485

Tariffs

Tariff meter

Reserve power supply

2 batteries, 2 batteries

Prepayment function

No, No

Options

Data protection by encryption, DLMS, DLMS, Voltage quality control, Load disconnection relay, Remote firmware change, Data protection by encryption, Remote firmware change, Voltage quality control, Load disconnection relay

Design features

Split case, One-piece case, One-piece case, Optoport cover protection, Optoport cover protection, RESET button with the possibility of sealing and parameterization, Transparent case, Transparent terminal cover, Split case, Transparent case, Transparent terminal cover, RESET button with the possibility of sealing and parameterization

Three-phase meter

Specifications

Accuracy class for measuring of active energy:
EN 62053-211
EN 62053-220,5 S (transformer connection)
Accuracy class for measuring of reactive energy:
EN 62053-232
Nominal voltage3х220/380;
3х230/400;
3х240/416 V
3х57,7/100 V – 3×240/416 V,
(Wide range, for transformer connection)
Operation voltage range-20 … +15%
Nominal frequency50 Hz
Nominal current5 А
Maximum current10 A; 80 A; 100 A; 120 A
Meter constant8000 imp / (kW*h)
Starting current for measuring of active energy :
for meters of direct conection class 1,012,5 mА
for meters of transformer conection class 1.0 (0.5 S)10 mА (5 mА)
Starting current for measuring of reactive energy :
for meters of direct conection class 1,015,6 mА
for meters of transformer conection class 1.0 (0.5 S)15,0 mА (9,3 mA)
Power consumption, no more than:
in the voltage circuits without PLC interface10 V•A (2 W)
in the voltage circuits with PLC interface20 V•A (5 W)
in current circuits0,05 V•A
Operating temperature-40 … +70 °C
Protection levelІР 54
Weight, no more than0,73 kg
Number of digits on LCD6 + 2
Battery life16 years
Service life24 years

 

Dimensions

Table of construction types